4-18
4-2 Function Mode
SYSDRIVE MX2 Series USER'S MANUAL (3G3MX2-A@@@@)
4
Parameter List
Electronic Thermal
b015
Free-electronic
Thermal
Frequency 1
0. to Free-electronic Thermal
Frequency 2
0. no yes Hz
5-112
b016
Free-electronic
Thermal Current 1
0.00 to Rated current 0.00 no yes A
b017
Free-electronic
Thermal
Frequency 2
Free-electronic Thermal
Frequency 1 to Free-
electronic Thermal Current 3
0. no yes Hz
b018
Free-electronic
Thermal Current 2
0.00 to Rated current 0.00 no yes A
b019
Free-electronic
Thermal
Frequency 3
Free-electronic Thermal
Frequency 2 to 400. (1000.)
0. no yes Hz
5-112
b020
Free-electronic
Thermal
Current 3
0.00 to Rated current 0.00 no yes A
Overload limit, Overcurrent Protection
b021
Overload Limit 1
Selection
00: Disabled
01: Enabled in acceleration/
constant speed operation
02: Enabled in constant speed
operation
03: Enabled during
acceleration/constant
speed operation
(accelerated during
regeneration)
01 no yes
−
5-114
b221
Overload Limit 2
Selection
01 no yes
b022
Overload Limit 1
Level
0.20 × Rated current to 2.00 ×
rated current (heavy load
setting)
0.20 × Rated current to 1.50 ×
rated current (light load
setting)
Rated
current
×
1.50
(heavy)
or 1.20
(light)
no yes A
b222
Overload Limit 2
Level
no yes A
b023
Overload Limit 1
Parameter
0.1 to 999.9
1000. to 3000.
1.0 no yes
s
b223
Overload Limit 2
Parameter
1.0 no yes
b024
Overload Limit 1
Selection 2
00: Disabled
01: Enabled in acceleration/
constant speed operation
02: Enabled in constant speed
operation
03: Enabled during
acceleration/constant
speed operation
(accelerated during
regeneration)
01 no yes −
b025
Overload Limit 1
Level 2
0.20 × Rated current to 2.00 ×
rated current (heavy load
setting)
0.20 × Rated current to 1.50 ×
rated current (light load
setting)
Rated
current
×
1.50
(heavy)
or 1.20
(light)
no yes A
Parameter
No.
Function name Monitor or data range
Default
setting
Set data
Data can
be set
during
RUN
Data can be
changed
during RUN
Unit
Page