4-2 Function Mode
SYSDRIVE MX2 Series USER'S MANUAL (3G3MX2-A@@@@)
4
Parameter List
Overload limit, Overcurrent Protection
b026
Overload Limit 1
Parameter 2
0.1 to 999.9
1000. to 3000.
1.0 no yes s 5-114
b027
Overcurrent
Suppression
Selection
00: Disabled
01: Enabled
00 no yes − 5-116
b028
Frequency Pull-
in Restart Level
0.20 × Rated current to 2.00 ×
rated current (heavy load
setting)
0.20 × Rated current to 1.50 ×
rated current (light load
setting)
Inverter
rated
current
no yes A
5-97
5-100
5-103
b029
Frequency Pull-
in Restart
Parameter
0.1 to 999.9
1000. to 3000.
0.50 no yes s
b030
Starting
Frequency at
Frequency Pull-
in Restart
Selection
00: Frequency at interruption
01: Maximum frequency
02: Set frequency
00 no yes −
Lock
b031
Soft Lock
Selection
00: Data other than b031
cannot be changed when
terminal SFT is ON.
01: Data other than b031 and
set frequency cannot be
changed when terminal
SFT is ON.
02: Data other than b031
cannot be changed.
03: Data other than b031 and
set frequency cannot be
changed.
10: Data can be changed
during RUN.
01 no yes − 5-84
Others
b033
Motor Cable
Length Code
Selection
5. to 20. 10. no yes − 5-145
b034
RUN Time/Power
ON Time Level
0. to 9999. (0 to 99990)
1000 to 6553 (100000 to
655350)
0. no yes h 5-124
b035
Rotation
Direction Limit
Selection
00: No direction limit
01: Only Forward is enabled
(Reverse is limited)
02: Only Reverse is enabled
(Forward is limited)
00 no no − 5-23
Parameter
No.
Function name Monitor or data range
Default
setting
Set data
Data can
be set
during
RUN
Data can be
changed
during RUN
Unit