EasyManua.ls Logo

Omron 3G3MX2 - Page 87

Omron 3G3MX2
440 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4-20
4-2 Function Mode
SYSDRIVE MX2 Series USER'S MANUAL (3G3MX2-A@@@@)
4
Parameter List
Others
b036
Reduced
Voltage Startup
Selection
0 (Reduced voltage startup
time: short) to 255 (Reduced
voltage startup time: long)
2noyes 5-58
b037
Display
Selection
00: Complete display
01: Individual display of
functions
02: User setting + b037
03: Data comparison display
04: Basic display
05: Monitor display only
04 no yes 5-88
b038
Initial Screen
Selection
000: Screen on which the
Enter key was last
pressed
001 to 060: d001 to d060
201: F001
202: Do not use this setting.
001 no yes 5-86
b039
User Parameter
Automatic
Setting
Function
00: Disabled
01: Enabled
00 no yes 5-177
Torque limit
b040
Torque Limit
Selection
00: Four-quadrant separate
setting
01: Terminal switching
02: Analog voltage input
03: Optional board
00 no yes
5-153
b041
Torque Limit 1
(Four-quadrant
Mode Forward
Power
Running)
0. to 200.
no (Torque limit disabled)
200. no yes
%
b042
Torque Limit 2
(Four-quadrant
Mode Reverse
Regeneration)
200. no yes
b043
Torque Limit 3
(Four-quadrant
Mode Reverse
Power
Running)
200. no yes
b044
Torque Limit 4
(Four-quadrant
Mode Forward
Regeneration)
200. no yes
b045
Torque
LADSTOP
Selection
00: Disabled
01: Enabled
00 no yes 5-155
b046
Reverse
Rotation
Prevention
Selection
00: Disabled
01: Enabled
00 no yes 5-157
Other
b049
Heavy Load/
Light Load
Selection
00: Heavy load mode
01: Light load mode
00 no no 5-13
Parameter
No.
Function name Monitor or data range
Default
setting
Set data
Data can
be set
during
RUN
Data can be
changed
during RUN
Unit
Page

Table of Contents

Other manuals for Omron 3G3MX2

Related product manuals