4-21
4-2 Function Mode
SYSDRIVE MX2 Series USER'S MANUAL (3G3MX2-A@@@@)
4
Parameter List
Controlled deceleration on power loss
b050
Controlled
Deceleration on
Power Loss
00: Controlled deceleration on
power loss disabled.
01: Controlled deceleration on
power loss enabled
(deceleration stop)
02: Controlled deceleration on
power loss (constant
voltage, without recovery)
03: Controlled deceleration on
power loss (constant
voltage, with recovery)
00 no no
5-106
b051
DC Bus Voltage
Trigger Level of
Ctrl. Decel.
0.0 to 999.9
1000.
220.0/
440.0
no no V
b052
Deceleration
Hold Level of
Ctrl. Decel
0.0 to 999.9
1000.
360.0/
720.0
no no V
b053
Deceleration
Time of Ctrl.
Decel
0.01 to 3600.00 1.0 no no s
b054
Freq. Drop to
Start Ctrl. Decel
0.00 to 10.00 (100.0) 0.00 no no Hz 5-106
Window comparator
b060
Window
Comparator FV
Upper Limit
Level
Set an upper limit level.
Setting range: 0. to 100.
Lower limit: Lower limit level +
Hysteresis width × 2
100. yes yes %
5-132
b061
Window
Comparator FV
Lower Limit
Level
Set a lower limit level. Setting
range: 0. to 100.
Upper limit: Upper limit level
Hysteresis width × 2
0. yes yes %
b062
Window
Comparator FV
Hysteresis
Width
Set a hysteresis width for the
upper and lower limit levels.
Setting range: 0. to 10.
Upper limit: (Upper limit level
Lower limit level)/2
0. yes yes %
b063
Window
Comparator FI
Upper Limit
Level
Set an upper limit level.Setting
range: 0. to 100.
Lower limit: Lower limit level +
Hysteresis width × 2
100. yes yes %
b064
Window
Comparator FI
Lower Limit
Level
Set a lower limit level.
Setting range: 0. to 100.
Upper limit: Upper limit level
Hysteresis width × 2
0. yes yes %
Window comparator
b065
Window
Comparator FI
Hysteresis Width
Set a hysteresis width for the
upper and lower limit levels.
Setting range: 0. to 10.
Upper limit: (Upper limit level
Lower limit level)/2
0. yes yes % 5-132
b070
Analog
Operation Level
at FV
Disconnection
0. to 100.
no (ignore)
no no yes
5-132
b071
Analog
Operation Level
at FI
Disconnection
0. to 100.
no (ignore)
no no yes
Parameter
No.
Function name Monitor or data range
Default
setting
Set data
Data can
be set
during
RUN
Data can be
changed
during RUN
Unit
Page

Table of Contents