4-22
4-2 Function Mode
SYSDRIVE MX2 Series USER'S MANUAL (3G3MX2-A@@@@)
4
Parameter List
Others
b075
Ambient
Temperature
−10. to 50. 40. yes yes °C5-127
b078
Integrated
Power Clear
Cleared with the Enter key
after changing to 01
00 yes yes −
5-7
b079
Integrated
Power Display
Scale
1. to 1000. 1. yes yes −
b082
Starting
Frequency
0.10 to 9.99 (100.) 0.50 no yes Hz 5-57
b083
Carrier
Frequency
2.0 to 15.0/10.0
(heavy load/light load or high
frequency)
* With derating
10.0/
2.0
(5.0)
no yes
kHz
5-51
b084
Initialization
Selection
00: Initialization disabled
01: Fault monitor clear
02: Initializes data
03: Fault monitor clear + Data
initialization
04: Do not set.
00 no no −
5-174
b085
Initialization
Data Selection
00: Do not change. 00 no no −
b086
Frequency
Conversion
Coefficient
0.01 to 99.99 1.00 yes yes − 5-4
b087
STOP Key
Selection
00: Enabled
01: Disabled
02: Only reset is enabled
00 no yes − 5-84
b088
Free-run Stop
Selection
00: 0 Hz restart
01: Frequency matching
restart
02: Frequency pull-in restart
00 no yes − 5-103
b089
Automatic
Carrier
Reduction
00: Disabled
01: Enabled/depends on
current
02: Enabled/depends on fin
temperature
01 no no − 5-52
b090
Usage Rate of
Regenerative
Braking
0.0 to 100.0 0.0 no yes % 5-141
b091 Stop Selection
00: Deceleration stop
01: Free-run stop
00 no yes − 5-24
b092
Cooling Fan
Operation
00: Always
01: Only during operation
(including 5 minutes after
power on/stop)
02: Depends on the fin
temperature
01 no yes −
5-127
b093
Cooling Fan
Total Operation
Time Clear
00: Total operation time count
01: Clear total operation time
00 no no −
Parameter
No.
Function name Monitor or data range
Default
setting
Set data
Data can
be set
during
RUN
Data can be
changed
during RUN
Unit
Page