4-23
4-2 Function Mode
SYSDRIVE MX2 Series USER'S MANUAL (3G3MX2-A@@@@)
4
Parameter List
Others
b094
Initialization
Target
Selection
00: All data
01: All data other than
terminals/communication
02: U*** registration function
only
03: Other than U***
registration function and
Display Selection (b037)
00 no no − 5-174
b095
Regenerative
Braking
Selection
00: Disabled
01: Enabled (Disabled while
stopped)
02: Enabled (Enabled while
operating and stopped)
00 no yes −
5-141
b096
Regenerative
Braking ON
Level
330 to 380
660 to 760
360/
720
no yes V
V/f free setting
b100
Free V/f
Frequency 1
0. to Free V/f Frequency 2 0. no no Hz
5-47
b101
Free V/f
Voltage 1
0.0 to 800.0 0.0 no no V
b102
Free V/f
Frequency 2
Free V/f Frequency 1 to Free
V/f Frequency 3
0. no no Hz
b103
Free V/f
Voltage 2
0.0 to 800.0 0.0 no no V
b104
Free V/f
Frequency 3
Free V/f Frequency 2 to Free
V/f Frequency 4
0. no no Hz
b105
Free V/f
Voltage 3
0.0 to 800.0 0.0 no no V
b106
Free V/f
Frequency 4
Free V/f Frequency 3 to Free
V/f Frequency 5
0. no no Hz
b107
Free V/f
Voltage 4
0.0 to 800.0 0.0 no no V
b108
Free V/f
Frequency 5
Free V/f Frequency 4 to Free
V/f Frequency 6
0. no no Hz
5-47
b109
Free V/f
Voltage 5
0.0 to 800.0 0.0 no no V
b110
Free V/f
Frequency 6
Free V/f Frequency 5 to Free
V/f Frequency 7
0. no no Hz
b111
Free V/f
Voltage 6
0.0 to 800.0 0.0 no no V
b112
Free V/f
Frequency 7
Free V/f Frequency 6 to 400.
(1000.)
0. no no Hz
b113
Free V/f
Voltage 7
0.0 to 800.0 0.0 no no V
Parameter
No.
Function name Monitor or data range
Default
setting
Set data
Data can
be set
during
RUN
Data can be
changed
during RUN
Unit
Page