4-24
4-2 Function Mode
SYSDRIVE MX2 Series USER'S MANUAL (3G3MX2-A@@@@)
4
Parameter List
Others
b120
Brake Control
Function
Selection
00: Disabled
01: Enabled
00 no yes −
5-143
b121
Brake Release
Wait Time
0.00 to 5.00 0.00 no yes s
b122
Acceleration
Wait Time
0.00 to 5.00 0.00 no yes s
b123 Stop Wait Time 0.00 to 5.00 0.00 no yes s
b124
Brake Wait
Time for
Confirmation
0.00 to 5.00 0.00 no yes s
b125
Brake Release
Frequency
0.00 to 99.99
100.0 to 400.0
0.00 no yes Hz
b126
Brake Release
Current
0.00 to 2.00 × Inverter rated
current
Inverter
rated
current
no yes A
b127
Break ON
Frequency
0.00 to 99.99
100.0 to 400.0
0.00 no yes Hz
b130
Overvoltage
Suppression
Function
Selection
During
Deceleration
00: Disabled
01: Enabled (DC voltage kept
constant)
02: Enabled (Acceleration
enabled)
00 no yes −
5-117
b131
Overvoltage
Suppression
Level During
Deceleration
200V class: 330. to 395.
400V class: 660. to 790.
380/
760
no yes V
b132
Overvoltage
Suppression
Parameter
0.10 to 30.00 1.00 no yes s
b133
Overvoltage
Suppression
Proportional
Gain Setting
0.00 to 5.00 0.20 yes yes −
b134
Overvoltage
Suppression
Integral Time
Setting
0.0 to 150.0 1.0 yes yes s
b145
GS Input
Operation
Selection
00: Not tripped (cut off by
hardware)
01: Tripped
00 no yes − 5-171
b150
Main Panel
Display
Selection
001 to 060 (corresponding to
d001 to d060)
001 yes yes − 5-87
b160
d050 Monitor
Target 1
001 to 030 (corresponding to
d001 to d030)
001 yes yes −
5-10
b161
d050 Monitor
Target 2
001 to 030 (corresponding to
d001 to d030)
002 yes yes −
b163
d001/d007
Frequency
Setting Mode
Selection
00: Disabled
01: Enabled
00 yes yes −
5-1
5-4
Parameter
No.
Function name Monitor or data range
Default
setting
Set data
Data can
be set
during
RUN
Data can be
changed
during RUN
Unit
Page