4-25
4-2 Function Mode
SYSDRIVE MX2 Series USER'S MANUAL (3G3MX2-A@@@@)
4
Parameter List
Others
b164
Initial Screen
Automatic
Switching
Function
00: Disabled
01: Enabled
00 yes yes − 5-87
b165
Selection of
Operation on
Digital Operator
Disconnection
00: Trip
01: Trip after deceleration stop
02: Ignored
03: Free-run stop
04: Deceleration stop
02 yes yes − 5-86
b171
Inverter Mode
Selection
00: Selection disabled
01: Induction motor
02: High-frequency induction
motor
00 no no − 5-178
b180
Perform
Initialization/
Mode Selection
00: Initialization disabled
01: Perform initialization/
mode selection
00 no no − 5-174
Password
b190
Password A
Setting
0000: Password function
disabled
0001 to FFFF: Password
0000 no no −
5-91
b191
Password A
Authentication
0000 to FFFF 0000 no no −
b192
Password B
Setting
0000: Password function
disabled
0001 to FFFF: Password
0000 no no −
b193
Password B
Authentication
0000 to FFFF 0000 no no −
Parameter
No.
Function name Monitor or data range
Default
setting
Set data
Data can
be set
during
RUN
Data can be
changed
during RUN
Unit
Page