9 - 17
9 LX inverter
Drive Programming User’s Manual (I580-E2)
9-5 Drive Programming Commands
9
9-5-2 Inverter Control Commands
Note The A052 parameter must be set to value 03 (Drive Programming) for the command to become effective.
Decel
Command Description Argument
Sets the inverter deceleration time.
This command is a (Assign) command whose
left-hand side is set to the deceleration time
variable DECEL.
Unit: 10 ms
Value: any variable or constant
(range 1 to 360,000)
Format
Flowchart method Text language method
DECEL : <value>