3 Operation Procedure for Drive Programming
3 - 18
Drive Programming User’s Manual (I580-E2)
Basically, even if the inverter detects a trip during the Drive Programming operation, the operation is
continued. However, if any of E43 to E45 trips related to the Drive Programming is detected, the opera-
tion is stopped.
Or, with the “on trip goto” command, the program can jump to other process after a trip occurred.
For details on the trips E43 to E59, refer to Section 8 Errors and Remedies.
3-3-6 Task Operation on Trip
With/without
“on trip goto”
Error status
User trip
E50 to E59
Drive Programming
related trip E43 to E45
Other trips
Without Operation is continued. Program is stopped. Operation is continued.
With After the “on trip goto”
command is executed, the
program jumps to the
specified label and the
operation is continued.
Program is stopped. After the “on trip goto”
command is executed, the
program jumps to the
specified label and the
operation is continued.