EasyManua.ls Logo

Omron CIMR-L7Z - Page 27

Omron CIMR-L7Z
225 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
EN-25
FF_CAL
Feed forward motor acceleration time active
Perform the complete tuning procedure
Abort the tuning by setting
n5-05 = 0.
FRL
Ref Missing
No speed was selected before the inverter start. Check the speed selection/start sequence.
GF
Ground Fault
The ground current at the Inverter output exceeded
50% of the Inverter rated output current and L8-09=1
(Enabled).
Remove the motor and run the Inverter without the
motor.
Check the motor for a phase to ground short.
Check the output current with a clampmeter to ver-
ify the DCCT reading.
Check the control sequence for wrong motor contac-
tor signals.
LF
Output Phase
Loss
An open-phase occurred at the Inverter output.
The fault is detected when the output current falls
below 5% of the inverter rated current and L8-07=1
Reset the fault after correcting its cause.
Check the motor and Inverter capacity.
OC
Over Current
The Inverters output current exceeded the over cur-
rent detection level.
Remove the motor and run the Inverter without the
motor.
Check the motor for a phase-to-phase short.
Verify the accel/decel times
•(C1-).
Check the Inverter for a phase-to-phase short at the
output.
OH
Heatsink Over-
temp
L8-03 = 0,1 or 2 and the temperature of the Inverter's
cooling fin exceeded the L8-02 value.
Check for dirt build-up on the fans or heatsink.
Reduce the ambient temperature around the drive.
Replace the cooling fan(s).
Inverter's Cooling Fan Stopped
L8-03 = 3 and the temperature of the Inverter's cool-
ing fin exceeded the L8-02 value.
OH1
Heatsink Max
Temp
The temperature of the Inverters heatsink exceeded
105 °C.
Check for dirt build-up on the fans or heatsink.
Reduce the ambient temperature around the drive.
Replace the cooling fan(s).
Inverter’s Cooling Fan Stopped
OL1
Motor Overload
Detected when L1-01 is set to 1,2 or 3 and the
Inverters output current exceeded the motor over-
load curve.
The overload curve is adjustable using parameter E2-
01 (Motor Rated Current), L1-01 (Motor Protection
Selection) and L2-02 (Motor Protection Time Con-
stant)
Recheck the cycle time and the size of the load as
well as the accel/decel times
•(C1-).
Check the V/f characteristics (E1-).
Check the setting of Motor Rated Current Setting
(E2-01).
OL2
Inv Overload
The Inverter output current exceeded the Inverters
overload capability.
Recheck the cycle time and the size of the load as
well as the accel/decel times
•(C1-).
Check the V/f characteristics (E1-).
Check the setting of Motor Rated Current Setting
(E2-01).
OS
Motor Over speed
Det
F1-03 = 0, 1 or 2 and A1-02 is set to 3 or 6.
The motor speed feedback (U1-05) exceeded the F1-
08 value for the time F1-09.or longer.
Adjust the ASR settings in the C5 parameter group.
Check the reference circuit and reference gain.
Check the settings in F1-08 and F1-09.
F1-03 = 3 and A1-02 is set to 3 or 6.
The motor speed feedback (U1-05) exceeded the F1-
08 value for the time F1-09.or longer.
OV
DC Bus Overvolt
(only in
stop
condi-
tion)
The DC bus voltage has exceeded the overvoltage
detection level.
Default detection levels are:
200 V class: 410 VDC
400 V class: 820 VDC
Increase the deceleration time (C1-02/04/06/08) or
connect a braking option.
Check the power supply and decrease the voltage to
meet the inverters specifications.
Check the braking chopper/resistor.
PF
Input Phase Loss
Too big DC bus voltage ripple.
Only detected when L8-05=1 (enabled)
Tighten the input terminal screws
Check the power supply voltage
PGO
PG Open
(PG Disconnec-
tion)
F1-02 = 0, 1 or 2 and A1-02 = 3 or 6
No PG (encoder) pulses are received for the time F1-
14 or longer.
Fix the broken/disconnected wiring.
Fix the wiring.
Supply power to the PG
•properly.
Check the sequence and if the brake is opened when
the inverter starts to increase the speed.
F1-02 = 3 and A1-02 = 3 or 6.
No PG (encoder) pulses are received for the time F1-
14 or longer.
Display
Displayed as
Meaning Corrective Actions
Alarm Fault

Table of Contents

Other manuals for Omron CIMR-L7Z

Related product manuals