12 Pulse Outputs
12-40
CP1E CPU Unit Software User’s Manual(W480)
PLC Setup
Note The interrupt input setting is read from the PLC Setup when the power supply is turned ON.
DM Area Settings
• Speed Control Settings to Feed Wrapping Material to Initial Position
• Positioning Control Settings for Wrapping Material
Preparations
Setting
Enable using built-in input IN4 as an interrupt input.
Setting Address Data
Acceleration/deceleration rate:
500 Hz/4 ms
D0 #01F4
Target frequency: 10,000 Hz D1 #2710
D2 #0000
Setting Address Data
Acceleration rate: 500 Hz/4 ms D10 #01F4
Deceleration rate: 500 Hz/4 ms D11 #01F4
Target frequency: 10,000 Hz D12 #2710
D13 #0000
Number of output pulses: 5,000
pulses
D14 #1388
D15 #0000
Starting frequency: 0 Hz D16 #0000
D17 #0000