17-29
17 Ethernet Option Board
CP1E CPU Unit Software User’s Manual(W480)
17-4 Memory Allocations
17
17-4-1 DM Area Allocation
If the password for accessing the Ethernet Option Board’s Web page is forgotten, find out it in this
area. It is written in ASCII format.
The IP address is (1)(2).(3)(4).(5)(6).(7)(8) (hex)
If the local IP address in the system setup is set to a value other than 0.0.0.0, this area will act as an
IP address display area and the local IP address in the system setup will be read and stored here
when the power is turned ON or the Ethernet Option Board restarted.
If the local IP address in the system setup is set to 0.0.0.0, this area will act as an IP address setting
area. The value will be read by the Ethernet Option Board when the power is turned ON or the
Ethernet Option Board restarted and is used as the local IP address.
If the IP address for accessing the Ethernet Option Board through Web browser is forgotten, find out it
in th
is area.
Note When IP address in system setup area and DM area are all set to 0.0.0.0, the IP address will be
192.168.250.1 (FINS node address).
HTTP Server Setup
Offset 15 8 7 0
D1449
HTTP Password
⋅⋅⋅
D1452
D1453 HTTP Port number
FINS Node Address
Using IP Address Display/Setting Area
D1454
FINS node address (hex)
The setting range is 0~ FE (hex).
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
D1455
D1456
(1)(2) (3)(4)
(5)(6) (7)(8)