A-57
Appendices
CP1E CPU Unit Software User’s Manual(W480)
A-2 Auxiliary Area Allocations by Address
App
A-2-1 Read-only Words
A281 00 Pulse Output 1
Accel/Decel Flag
This flag will be ON when pulses are
being output from pulse output 1
according to an ORG, ACC or PLS2
instruction and the output frequency is
being changed in steps (accelerating
or decelerating).
Cleared when operation starts or
stops.
OFF: Constant speed
ON: Accelerating or decelerating
Cleared Refreshed
each cycle
during the
overseeing
processes.
01 Pulse Output 1
Overflow/Underflow
Flag
This flag indicates when an overflow or
underflow has occurred in the pulse
output 1 PV.
Cleared when operation starts.
OFF: Normal
ON: Overflow or underflow
Cleared Refreshed
when the PV
is changed
by the INI
instruction.
Refreshed
when an
overflow or
underflow
occurs.
02 Pulse Output 1
Output Amount Set
Flag
ON when the number of output pulses
for pulse output 1 has been set with the
PULS instruction.
Cleared when operation starts or
stops.
OFF: No setting
ON: Setting made
Cleared Refreshed
when the
PULS
instruction is
executed.
Refreshed
when pulse
output stops.
03 Pulse Output 1
Output Completed
Flag
ON when the number of output pulses
set with the PULS or PLS2 instruction
has been output through pulse output
1.
Cleared when operation starts or
stops.
OFF: Output not completed.
ON: Output completed.
Cleared Refreshed at
the start or
completion of
pulse output.
04 Pulse Output 1
Output In-progress
Flag
ON when pulses are being output from
pulse output 1.
Cleared when operation starts or
stops.
OFF: Stopped
ON: Outputting pulses.
Cleared Refreshed
when pulse
output starts or
stops.
05 Pulse Output 1 No-ori-
gin Flag
ON when the origin has not been
determined for pulse output 1 and goes
OFF when the origin has been deter-
mined.
Turned ON when power is turned
ON.
Turned ON when operation starts.
OFF: Origin established.
ON: Origin not established.
Cleared Refreshed
each cycle
during over-
seeing pro-
cesses.
06 Pulse Output 1
At-origin Flag
ON when the pulse output 1 PV
matches the origin (0).
OFF: Not stopped at origin.
ON: Stopped at origin.
Cleared Refreshed
each cycle
during over-
seeing pro-
cesses.
07 Pulse Output 1
Output Stopped Error
Flag
ON when an error occurred while out-
putting pulses in the pulse output 1 ori-
gin search function.
The Pulse Output 1 Output Stop Error
code will be written to A445.
OFF: No error
ON: Stop error occurred.
Cleared Refreshed
when origin
search
starts.
Refreshed
when pulse
output stop
error occurs.
Address
Name Function Settings
Status
after
mode
change
Status at
startup
Write
timing
Related
flags,
settings
Words Bits