181
Error History Function Section 8-2
0374 Communications error 10 hex: Word Input Slave Unit,
Word I/O Slave Unit
20 hex: Word Output Slave
Unit
40 hex: Bit Input Slave Unit,
Bit I/O Slave Unit
50 hex: Bit Output Slave Unit
70 hex: Repeater Unit
Node address (hex) ×
0375 Communications have stopped due to a
communications error.
[Cause]
A communications error occurred while
communications were set to be
stopped.
10 hex: Word Input Slave Unit,
Word I/O Slave Unit
20 hex: Word Output Slave
Unit
40 hex: Bit Input Slave Unit,
Bit I/O Slave Unit
50 hex: Bit Output Slave Unit
Node address (hex)
0376 Address duplication error 10 hex: Word Input Slave Unit,
Word I/O Slave Unit
20 hex: Word Output Slave
Unit
40 hex: Bit Input Slave Unit,
Bit I/O Slave Unit
50 hex: Bit Output Slave Unit
70 hex: Repeater Unit
Node address (hex) ×
0378 Illegal Repeater Unit/configuration error 10 hex: Word Input Slave Unit,
Word I/O Slave Unit
20 hex: Word Output Slave
Unit
40 hex: Bit Input Slave Unit,
Bit I/O Slave Unit
50 hex: Bit Output Slave Unit
70 hex: Repeater Unit
Node address (hex) ×
0601 Illegal interrupt 00 00
0602 Special I/O Unit memory error 01 hex: Read error
02 hex: Write error
01 hex: Network parameters
02 hex: Software Setting Table
04 hex: Slave Unit parameters
06 hex: Error history
09 hex: Identity information
0A hex: Registration Table
(Error
his-
tory
only:
x)
Error
code
(hex)
Error contents Detailed information EEP
ROM
First byte Second byte

Table of Contents