187
FINS Commands Addressed to CompoNet Master Units and Responses Appendix A
Executes an echoback test between specified nodes.
Command Format
Response Format
End Codes (MRES/SRES)
Parameter Details
Test Data (Command)
The destination address is the address specified by the FINS header.
Test Data (Response)
The test data sent in the command is returned from the remote node just as it is.
If the test data contents are different, an error occurred.
ECHOBACK TEST 0801
MRC
08
SRC
01
Test data
1B 1B 1 to 538B
MRC
08
SRC
01
MRES SRES Test data
1B 1B 1B 1B 1 to 538B (Data specified in command)
End code (hex) Contents
0000 Normal completion
1001 The maximum permissible command length was exceeded.
1002 The command length is less than the minimum command length.