■ Wiring Example
Setup (For details, refer to Section 3.)
G9SX-BC: Manual reset, Cross fault detection mode: ON (Category 4 Wiring)
G9SX-GS: Manual reset, Cross fault detection mode: ON (Category 4 Wiring), Logical AND connections,
No OFF-delay time setting
Switching mode: Auto
Diagnostic check of Indicator: Enabled (UA only)
Wiring Example
S1 : Emergency Stop Switch
S2, S7 : Reset switch
S3 : Lock release switch
S4 : Guard Lock Door Switch
S5, S6 : Limit Switch
KM1 to KM4 : Contactor
M1 to M2 : 3-phase motor
Note: This example corresponds to category 4.