1-2 Advanced Unit
G9SX-AD
Note: 1. Internal power supply circuit is not isolated.
2. Logical AND input is isolated.
3. Outputs S14 to S54 are internally redundant.
G9SX-ADA
Note: 1. Internal power supply circuit is not isolated.
2. Logical AND input is isolated.
3. Outputs S14 to S54 are internally redundant.
Signal name Terminal name Wiring
Power supply inputs A1, A2
Connect the power supply plus (24 VDC) to the
A1 terminal.
Connect the power supply minus (GND) to the A2
terminal.
Safety inputs T11, T12, T21, T22
Refer to 2-4 Cross Fault Detection and 2-5
Connecting Safety Sensors and the G9SX
Feedback/reset inputs T31, T32, T33 Refer to 2-3 Reset Mode.
Logical AND connection inputs T41, T42, T51, T52 Refer to 2-1 Logical AND Connection.
Cross fault detection input Y1 Refer to 2-4 Cross Fault Detection.
Instantaneous safety outputs S14, S24, S34 Keep these outputs open when they are not used.
OFF-delayed safety outputs S44, S54 Keep these outputs open when they are not used.
Logical AND connection output L1, L2 Refer to 2-1 Logical AND Connection.
Auxiliary monitor outputs X1, X2 Keep these outputs open when they are not used.