2. Characteristics
G9SX
USER'S GUIDE
79
Ratings and SpecificationsSection 4
2-4 Expansion Unit
Note: 1. When two or more Units are connected by logical AND, the operating time and response time are the sum total of the operating times and response
times, respectively, of all the Units connected by logical AND.
2. This does not include the operating time or response time of Safety Guard Switching Units (G9SX-AD/-ADA/-NSA/-GS) that are connected.
3. This does not include the operating time or response time of internal relays in the G9SX-EX-@.
4. For the G9SX-@-RT (with screw terminals) only.
Item Model G9SX-EX-@
Overvoltage category (IEC/EN 60664-1) II (Safety relay outputs 13 to 43 and 14 to 44: III)
Operating time (OFF to ON state)
(See note 1.)
30 ms max. (See note 2.)
Response time (ON to OFF state)
(See note 1.)
10 ms max. (See note 2.)
ON-state residual voltage 3.0 V max. for safety outputs and auxiliary outputs
OFF-state leakage current 0.1 mA max. for safety outputs and auxiliary outputs
Maximum wiring length of safety input
and logical AND input
100 m max.
(External connection impedance: 100 Ω max. and 10 nF max.)
Reset input time (Reset button pressing
time)
100 ms min.
Accuracy of OFF-delay time (See note 3.) Within ± 5% of the set value
Insulation
resistance
Between all terminals
connected together and DIN
rail
100 MΩ min. (at 500 VDC)
Dielectric
strength
Between all terminals
connected together and DIN
rail
1,200 VAC for 1 min
Between different poles of
outputs
Between safety relay outputs
connected together and
other terminals connected
together
2,200 VAC for 1 min
Vibration resistance Frequency: 10 to 55 to 10 Hz, 0.375-mm single amplitude (0.75-mm double amplitude)
Shock
resistance
Destruction 300 m/s
2
Malfunction 100 m/s
2
Durability
Electrical
100,000 cycles min.
(rated load, switching frequency: 1,800 cycles/hour)
Mechanical 5,000,000 cycles min. (switching frequency: 7,200 cycles/hour)
Ambient operating temperature 10 to 55°C (with no icing or condensation)
Ambient operating humidity 25% to 85%
Terminal tightening torque (See note 4.) 0.5 N·m
Weight Approx. 165 g