Ratings and SpecificationsSection 4
2. Characteristics
78
G9SX
USER'S GUIDE
2-3 Safety Guard Switching Unit
Note: 1. When two or more Units are connected by logical AND, the operating time and response time are the sum total of the operating times and response
times, respectively, of all the Units connected by logical AND.
2. Represents the operating time when the safety input turns ON with all other conditions set.
3. Represents the operating time when the logical AND input turns ON with all other conditions set.
4. This is the allowable switching time for the operating mode selector. If switching takes more than 450 ms, the G9SX-GS@ will detect an error.
5. This is the time required for the safety input to actually switch to an activated condition after the mode selector input is switched.
6. Only when the G9SX-GS@ is used with manual switching.
7. For the G9SX-@-RT (with screw terminals) only.
Item Model G9SX-GS226-T15-@
Overvoltage category (IEC/EN 60664-1) II
Operating time (OFF to ON state)
(See note 1.)
50 ms max. (Safety input: ON) (See note 2.)
100 ms max. (Logical AND connection input: ON) (See note 3.)
Response time (ON to OFF state)
(See note 1.)
15 ms max.
Allowable switching time for mode
selector input (See notes 4 and 6.)
450 ms max.
Response time for switching operating
modes (See notes 5 and 6.)
50 ms max.
ON-state residual voltage 3.0 V max. for safety outputs, auxiliary outputs, and external indicator outputs
OFF-state leakage current 0.1 mA max. for safety outputs and auxiliary outputs, 1 mA max. for external indicator outputs
Maximum wiring length of safety input
and logical AND input
100 m max.
(External connection impedance: 100 Ω max. and 10 nF max.)
Reset input time
(Reset button pressing time)
100 ms min.
Accuracy of OFF-delay time Within ± 5% of the set value
Insulation
resistance
Between logical AND
connection terminals, and
power supply input terminals
and other input and output
terminals connected together
20 MΩ min. (at 100 VDC)
Between all terminals
connected together and DIN
rail
Dielectric
strength
Between logical AND
connection terminals, and
power supply input terminals
and other input and output
terminals connected together
500 VAC for 1 min
Between all terminals
connected together and DIN
rail
Vibration resistance Frequency: 10 to 55 to 10 Hz, 0.375-mm single amplitude (0.75-mm double amplitude)
Shock
resistance
Destruction 300 m/s
2
Malfunction 100 m/s
2
Ambient operating temperature 10 to 55°C (with no icing or condensation)
Ambient operating humidity 25% to 85%
Terminal tightening torque (See note 7.) 0.5 N·m
Weight Approx. 240 g
M1
M2
UA
UB
450 ms max.
50 ms max.
Safety input A is activated
Safety input B is activated
M1
M2
UA
UB
450 ms max.
50 ms max.
Safety input A is activated
Safety input B is activated
<When M2 Is Turned ON after M1 Is Turned OFF> <When M1 Is Turned OFF after M2 Is Turned ON>