2-2 Advanced Unit
This Unit has safety OFF-delayed outputs and can be connected to other Units using the logical AND connection
input and output.
■ G9SX-AD@
Safety Inputs
Safety Outputs (Semiconductor Outputs)
Note: The OFF-delayed outputs can be used as instantaneous outputs by
setting the OFF-delay time to 0 s.
Logical AND Connections
OFF-delay Time Setting
Required Settings and Wiring
LED Indicators
Safety inputs 1 input (2-channel input)
Safety input devices
Emergency stop switch, door switch,
light curtain
Instantaneous outputs
3 outputs
OFF-delayed outputs
2 outputs
Number of inputs 1 input
Number of outputs 1 output
G9SX-AD322-T15-@ 0 to 15 s
G9SX-AD322-T150-@ 0 to 150 s
Item G9SX-AD Page
Logical AND connection
input enable/disable
❍ 57
Cross fault detection mode ❍ 63
Reset mode ❍ 62
OFF-delay time ❍ 65
Switching mode --- ---
External indicator fault
diagnosis mode
--- ---
Safety Input
Safety
Instantaneous
Output
Safety
OFF-delayed
Output
Logical AND
Connection
Output
Logical AND
Connection
Input
No.
OFF-DELAY
0.5
0.4
0.3
0.2
15
10
7
5
4
3
2
1.5
1
0.6
0.7
0
S54S44S34S24S14 L1
A2T42T41T22T21
A1X2X1Y1T12T11
T33T31
T1
ERR
EI
AND
FB
ED
T2
PWR
T32
G9SX-AD322-T15
24VDC
Marking Color Name
PWR Green Power supply indicator
T1 Orange Safety input #1 indicator
T2 Orange Safety input #2 indicator
FB Orange Feedback/reset input indicator
AND Orange Logical AND input indicator
EI Orange Safety output indicator
ED Orange
OFF-delayed safety output
indicator
ERR Red Error indicator