2-11 Confirming Settings
Settings for the G9SX can be checked by the orange indicators for approx. 3 seconds after the power is turned ON.
During this settings indication period, the ERR indicator will light, however the auxiliary error output will remain OFF.
G9SX-AD/-ADA/-BC/-NS/-NSA
Note: Except for the G9SX-BC and G9SX-NS.
G9SX-GS
Indicator Item Setting position
Indicator
status
Setting mode Setting status
T1
Cross fault detection
mode
Y1 terminal
Lit Detection mode Y1 = open
Not lit Non-detection mode Y1 = 24 VDC
FB Reset mode
T33 or T32
terminal
Lit Manual reset mode T33 = 24 VDC
Not lit Auto reset mode T32 = 24 VDC
AND
(AND1,
AND2)
Logical AND connection
input mode (See note.)
Logical AND
connection preset
switch
Lit Enable logical AND input "AND"
Not lit Disable logical AND input "OFF"
Indicator Item Setting position
Indicator
status
Setting mode Setting status
T1
Cross fault detection
mode for safety input A
Y1 terminal
Lit Enabled Y1 = open
Not lit Disabled Y1 = 24 VDC
T6
Cross fault detection
mode for safety input B
Y2 terminal
Lit Enabled Y2 = open
Not lit Disabled Y2 = 24 VDC
FB Reset mode
T33 or T32
terminal
Lit Manual reset mode T33 = 24 VDC
Not lit Auto reset mode T32 = 24 VDC
AND
Logical AND connection
input mode
Logical AND
connection preset
switch
Lit Enabled "AND"
Not lit Disabled "OFF"
UA, UB Switching Function
Switching Function
setting switch
Lit Manual switching "Manual"
Not lit Auto switching "Auto"