Wiring and SetupSection 3
2. Functions, Wiring and Settings
60
G9SX
USER'S GUIDE
2-2 Response Time and Operation Time
(1) G9SX-BC
(2) G9SX-AD/ADA
(3) G9SX-NS
(4) G9SX-NSA
Note: 1. The maximum response time is the time it takes the output to turn OFF after the input turns OFF.
2. The maximum operating time is the time it takes the output to turn ON after the input turn ON.
Safety input
Max. response time
(excluding Expansion Units)
(See note 1.)
Max. operating time
(excluding Expansion Units)
(See note 2.)
Safety input 15 ms 50 ms
Safety input
D4NS
Logical AND
connection input
Max. response time
(excluding Expansion Units)
(See note 1.)
Max. operating time
(excluding Expansion Units)
(See note 2.)
Safety input 15 ms 50 ms
Logical AND connection
input
15 ms 100 ms
Non-contact Door
Switch input
D40A
Logical AND
connection input
Max. response time
(excluding Expansion Units)
(See note 1.)
Max. operating time
(excluding Expansion Units)
(See note 2.)
Non-contact Door Switch
input
20 ms 100 ms
Logical AND connection
input
15 ms 100 ms
Safety Input
D4NS
Logical AND
connection input
Non-contact Door
Switch input
D40A
Max. response time
(excluding Expansion Units)
(See note 1.)
Max. operating time
(excluding Expansion Units)
(See note 2.)
Non-contact Door Switch
input
20 ms 100 ms
Safety input 15 ms 50 ms
Logical AND connection
input
15 ms 100 ms