Variable name _EIP_TagAdrErr
Meaning Tag Name Resolution Error Global/local Global
Function NX-series CPU Units: Indicates that the tag resolution for CIP communications 1 failed (i.e., the address could not
be identified from the tag name).
TRUE: T
ag resolution failed (i.e., the address could not be identified from the tag name). The following causes are
possible.
• The size of the network variable is different from the tag settings.
• The I/O direction that is set in the tag data link settings does not agree with the I/O direction of the variable in
the CPU Unit.
• There is no network variable in the CPU Unit that corresponds to the tag setting.
FALSE: Other than the above.
NJ-series CPU Units: Indicates that tag name resolution failed (i.e., the address could not be identified from the
tag name).
TRUE: Tag resolution failed (i.e., the address could not be identified from the tag name). The following causes are
possible.
• The size of the network variable is different from the tag settings.
• The I/O direction that is set in the tag data link settings does not agree with the I/O direction of the variable in
the CPU Unit.
• There is no network variable in the CPU Unit that corresponds to the tag setting.
FALSE: Other than the above.
Data type BOOL Range of values TRUE or FALSE
R/W access R Retained Not retained. Network Publish Published.
Usage in user pro-
gram
Possible. Related in-
structions
---
Variable name _EIP1_TagAdrErr
Meaning CIP Communications1 Tag Name Resolution
Error
Global/local Global
Function Indicates that the tag resolution for CIP communications 1 failed (i.e., the address could not be identified from the
tag name).
TRUE: T
ag resolution failed (i.e., the address could not be identified from the tag name). The following causes are
possible.
• The size of the network variable is different from the tag settings.
• The I/O direction that is set in the tag data link settings does not agree with the I/O direction of the variable in
the CPU Unit.
• There is no network variable in the CPU Unit that corresponds to the tag setting.
FALSE: Other than the above.
Note You can use this system-defined variable only for NX-series CPU Units.
Data type BOOL Range of values TRUE or FALSE
R/W access R Retained Not retained. Network Publish Published.
Usage in user pro-
gram
Possible. Related in-
structions
---
3 System-defined Variables Related to the Built-in EtherNet/IP Port
3-49
NJ/NX-series CPU Unit Built-in EtherNet/IP Port User’s Manual (W506)
3-3 Specifications for Individual System-defined Varia-
bles
3

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron NX102-12 Series and is the answer not in the manual?

Omron NX102-12 Series Specifications

General IconGeneral
BrandOmron
ModelNX102-12 Series
CategoryController
LanguageEnglish

Related product manuals