EasyManua.ls Logo

Omron NX1P2 series

Omron NX1P2 series
264 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Communications lines and power lines
DC signals and AC signals
High-frequency devices (such as Inverters) and signal lines (communications)
l
Wiring
Observe the following points when wiring power supply and signal cables.
When routing signal cables with differing characteristics through the same duct, always keep
them separated.
As much as possible, avoid routing multiple power supply lines through the same duct.
If it cannot be avoided, then construct a partition between them in the duct and ground the parti-
tion.
Partitioning Methods for Signal and Power Supply Cables
(a) (b)
(c) (d)
Signal cables
Signal cables
Signal cables
Power supply cables
Power
supply
cables
Power supply cables
Partition
Signal
cables
(group A)
Signal
cables
(group B)
Signal
cables
(group C)
To avoid overheating the conduits when using conduits for wiring, do not place wires for a single
circuit in separate conduits.
Parallel Wiring (Single Phase)
Correct
Correct
Power supply
Incorrect
Power supply
Power supply
Load
Load
Load
Conduits
Conduits
Conduits
OK
OK
NG
Power cables and signal cables adversely affect each other. Do not wire them in parallel.
5 Installation and Wiring
5-89
NX-series NX1P2 CPU Unit Hardware Users Manual (W578)
5-5 Control Panel Installation
5
5-5-5 Electrical Environment

Table of Contents

Other manuals for Omron NX1P2 series

Related product manuals