If the Fail-soft Operation Setting is set to Stop, process data communications will stop for all
slaves when an EtherCAT communications error is detected in a slave. At that time, the Servo Drive
will operate according to the Servo Drive specifications. Make sure that the Fail-soft Operation
setting
results in safe operation when a device error occurs.
EtherCAT communications are not always established immediately after the power supply is turned
ON. Use the system-defined variables in the user program to confirm that communications are es-
tablished before attempting control operations.
If noise occurs or an EtherCAT slave is disconnected from the network, any current communications
frames may be lost. If frames are lost, slave I/O data is not communicated, and unintended opera-
tion may occur. The slave outputs will behave according to the slave specifications. Refer to the
manual for the slave. If a noise countermeasure or slave replacement is required, perform the fol-
lowing processing.
a) Program the Input Data Invalid system-defined variable as an interlock condition in the user pro-
gram.
b) Set the PDO communications timeout detection count setting in the EtherCAT master to at
least 2. Refer to the NJ/NX-series CPU Unit Built-in EtherCAT Port User’s Manual (Cat. No.
W505) for details.
When an EtherCAT slave is disconnected, communications will stop and control of the outputs will
be lost not only for the disconnected slave, but for all slaves connected after it through to the physi-
cal end node. Confirm that the system will not be adversely affected before you disconnect a slave.
I/O data communications of NX bus are not always established immediately after the power supply
is turned ON. Use the system-defined variables and the EtherCAT Coupler Unit device variables in
the user program to confirm that I/O data communications are established before attempting control
operations.
You cannot use standard Ethernet hubs or repeater hubs with EtherCAT communications. If you use
one of these, a major fault level error or other error may occur.
Confirm that all of the slaves are connected before you set the transmission delay time by the actual
measurement. If the transmission delay time is exceeded from the set values due to the changes of
the unit configuration, such as when the disabled salve is connected to the actual configuration after
the setting, it may cause illegal communications with slaves.
When the communications cable that is connected to the slave from other manufacturers on the ring
topology is broken or the power supply to the slave from other manufacturers is interrupted, any cur-
rent communications frames may be lost.
If frames are lost, slave I/O data is not communicated, and unintended operation may occur.
When slaves from other manufacturers are connected on the ring topology, check the followings in
advance.
a) Disconnect and connect communications cables that are connected to the output ports of slaves
from other manufacturers several times, and there is no error except for a Ring Disconnection
Detected.
b) Disconnect and connect communications cables that are connected to the input ports of slaves
from other manufacturers several times, and there is no error except for a Ring Disconnection
Detected.
c) Turn OFF and ON the power supply to the slaves from other manufacturers, and there is no er-
ror except for a Illegal Slave Disconnection Detected.
If you use the cable redundancy function, confirm that the task execution time is within the task peri-
od while the cable for the end port of the ring is disconnected. When a disconnection occurred on
Precautions for Safe Use
26
NX-series NX1P2 CPU Unit Hardware Users Manual (W578)

Table of Contents

Other manuals for Omron NX1P2 series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron NX1P2 series and is the answer not in the manual?

Omron NX1P2 series Specifications

General IconGeneral
ModelNX1P2 Series
ManufacturerOmron
TypeController
CPU Units1
Program Capacity5 MB
Data Memory Capacity128 KB
Ethernet Ports1
Serial Ports1
Built-in EtherNet/IP PortYes
Built-in EtherCAT PortYes
Built-in USB PortYes
SD Memory Card SlotYes
USB Port1
Power Supply Voltage24 VDC
Programming LanguageLadder, Structured Text, Function Block Diagram
Communication ProtocolsEtherNet/IP, EtherCAT, Serial (RS-232C)