Transferring Programs
If you use the program transfer from SD Memory Card, set to enter the password for each execution
to prevent an unexpected program transfer.
Replacing Slaves and Units
If you replace a slave or Unit, refer to the operation manual for the slave or Unit for information on
the data required for individual slaves or Units and redo the necessary settings.
Task Settings
If a Task Period Exceeded error occurs, shorten the programs to fit in the task period or increase the
setting of the task period.
Motion control
Use the system-defined variable in the user program to confirm that EtherCAT communications are
established before you attempt to execute motion control instructions. Motion control instructions are
not executed normally if EtherCAT communications are not established.
Use the system-defined variables to monitor for errors in communications with the slaves that are
controlled by the motion control function module. Motion control instructions are not executed nor-
mally if an error occur in slave communications.
Before you start an MC Test Run, make sure that the operation parameters are set correctly.
Do not download motion control settings during an MC Test Run.
EtherCAT Communications
If you need to disconnect the cable from an EtherCAT slave during operation, first disconnect the
software connection to the EtherCAT slave or disable the EtherCA
T slave and all of the EtherCAT
slaves that are connected after it.
Set the Servo Drives to stop operation if an error occurs in EtherCAT communications between the
Controller and a Servo Drive.
Make sure that all of the slaves to be restored are participating in the network before you reset a
Network Configuration Verification Error, Network Configuration Verification Error (Mismatched
Slave), Network Configuration Verification Error (Slave Unconnected), Network Configuration Verifi-
cation Error (Unnecessary Slave Connected), Network Configuration Verification Error (Incorrect
Ring Wiring), Process Data Communications Error, Illegal Slave Disconnection Detected or Link
OFF Error in the EtherCAT Master Function Module. If any slave is not participating when any of
these errors is reset, the EtherCAT Master Function Module may access salve with a different node
address than the specified node address or the error may not be reset correctly.
Always use the specified EtherCAT slave cables. If you use any other cable, the EtherCAT master
or the EtherCAT slaves may detect an error and one of the following may occur.
a) Continuous refreshing of process data communications will not be possible.
b) Continuous refreshing of process data communications will not end during the set cycle.
Precautions for Correct Use
33
NX-series NX1P2 CPU Unit Hardware Users Manual (W578)

Table of Contents

Other manuals for Omron NX1P2 series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron NX1P2 series and is the answer not in the manual?

Omron NX1P2 series Specifications

General IconGeneral
ModelNX1P2 Series
ManufacturerOmron
TypeController
CPU Units1
Program Capacity5 MB
Data Memory Capacity128 KB
Ethernet Ports1
Serial Ports1
Built-in EtherNet/IP PortYes
Built-in EtherCAT PortYes
Built-in USB PortYes
SD Memory Card SlotYes
USB Port1
Power Supply Voltage24 VDC
Programming LanguageLadder, Structured Text, Function Block Diagram
Communication ProtocolsEtherNet/IP, EtherCAT, Serial (RS-232C)

Related product manuals