124
Analog Input Units Section 5-4
One-shot Time Setting
1,2,3... 1. Input the desired value in the SHOT Off Delay Field on the Top/Valley Tab
Page in the Function Choice Area.
2. Return to the General Tab Page, click the Download Button, and then
click the Reset Button to reset the Unit.
3. Click the OK Button to exit.
Rate of Change 
Calculation
The rate of change can be obtained for each sampling cycle set for the analog
input data. This function calculates the difference between each set sampling
cycle and value obtained in the previous cycle. The default setting for the
sampling cycle is 100 ms and the sampling cycle setting range depends on
the model, as shown in the following table. 
Note If the sampling cycle is set to a small value, the rate of change will be sensi-
tive to small changes. If the analog data is subject to minute fluctuations, and
the sampling cycle is shorter than the cycle of fluctuation, the fluctuation will
Model Sampling cycle setting range
GRT1-AD2 10 to 65,530 ms (Set in 10-ms units.)
0 
Analog input value
Analog data
Rate of change
Time
Deviation data