Analog Input Units Section 5-4
be regarded as the rate of change. To prevent this occurring, use moving
average processing, which will set a longer sampling cycle. 
Setting Procedure (Example: DeviceNet Configurator)
1,2,3... 1. In the Network Configuration Window for the Slice I/O Terminal, double-
click the icon of the Slice I/O Terminal that is to be set. Alternatively, right-
click the icon and select Parameters - Edit. The Edit Device Parameters
Window will be displayed.
2. Click the I/O Module Tab.
3. Click the Edit Button on the I/O Module Tab Page. The Edit Unit Parame-
ters Window will be displayed.
4. Select the tab page for the input where rate of change is to be set, and se-
lect the Rate of Change Check Box in the Function Choice Area.
Desired gradient
Fluctuation in analog value
Short sampling cycle
Long sampling cycle