174
Temperature Input Units Section 6-4
5. Double-click the Value Setting for the Input Type on the Range/Data Allo-
cation Tab Page and select the desired input type from the pull-down
menu. 
6. Return to the General Tab Page, click the Download Button, and then
click the Reset Button to reset the Unit.
7. Click the OK Button to exit the window.
Note The Input Type cannot be changed from the Setting Tool if the mode for set-
ting the Input Type with the DIP switch has been specified. 
Input Type Range The input type range can be set with the DIP switch or the Setting Tool.
GRT1-TS2P
GRT1-TS2PK
Note The ranges in the above table are the ranges for which the speci-
fied accuracy applies. 
GRT1-TS2T
 Input type
Range in °C Range in °F
PT100 (
−200 to 850°C) −200.0 to 850.0 −300 to 1,500
PT100 (
−200 to 200°C) −200.0 to 200.0 −300 to 380.0
 Input type
Range in 
°C Range in °F
PT1000 (
−200 to 
850°C)
−200.0 to 850.0 −300 to 1,500
PT1000 (
−200 to 
200°C)
−200.0 to 200.0 −300 to 380.0
 Input type
Range in 
°C Range in °F
R 0 to 1,700 0 to 3,000
S 0 to 1,700 0 to 3,000
K (−200 to 1300°C)
−200 to 1,300 −300 to 2,300
K (0.0 to 500.0°C) 0.0 to 500.0 0.0 to 900.0
J (−100 to 850°C)
−100 to 850 −100 to 1,500
J (0.0 to 400.0°C) 0.0 to 400.0 0.0 to 750.0
T
−200.0 to 400.0 −300.0 to 700.0
E 0 to 600 0 to 1,100