Temperature Input Units Section 6-4
User Adjustment A user adjustment can be set to compensate for an offset in the input value
caused by factors such as the characteristics and connection methods of the
input sensor.
Note (1) Temperature Input Units are properly adjusted at the factory before ship-
ment, so it is normally unnecessary to make adjustments. Use the user
adjustment only when absolutely necessary. OMRON is not responsible
for the results of user adjustment. If a mistake is made in the adjustment,
the adjustment data can be cleared to return to the factory default set-
tings.
(2) The Temperature Input Unit continues the temperature conversion oper-
ations even after user adjustment has been made. It is possible for tem-
perature data values to change suddenly from previous values after the
user adjustment is made, so always consider the effects on the operating
environment before applying the user adjustment.
100%
0%
Conversion data
After adjustment
Before
adjustment
Temperature input value