EasyManua.ls Logo

Omron SmartSlice GRT1 Series - Page 328

Omron SmartSlice GRT1 Series
366 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
308
Explicit Messages Appendix A
Setting and Monitoring Output Terminals
Explicit
message
Read/
write
Function Command Response
Service
code
Class
ID
Instance
ID
Attribute
ID
Data size
Terminal
Mainte-
nance Infor-
mation
Monitor
Mode
Read Reads the specified
output’s monitor
mode for mainte-
nance information.
0E hex 8E hex 01 to 40
hex
*1
85 hex --- 4 bytes
0: Total ON
time mode
1: Contact oper-
ation counter
mode
The mode is
read for out-
puts 0 to 32.
*10
Write Writes the specified
output’s monitor
mode for mainte-
nance information.
10 hex 8E hex 01 to 40
hex
*1
85 hex 4 bytes
0: Total ON
time mode
1: Contact oper-
ation counter
mode
The mode is set
for outputs 0 to
32.
*10
Set all
other bits to 0.
---
Set Value
of Output
Mainte-
nance
Counter
Read Reads the set value
for the total ON time
(unit: s) or number
of contact opera-
tions (unit: opera-
tions) the output (0
to 3, or 0 to 7 for an
Eight-output Unit)
specified by the
Attribute ID.
0E hex 8E hex 01 to 40
hex
*1
78 hex
*2
7B hex
*3
7E hex
*4
81 hex
*5
A8 hex
*6
AB hex
*7
AE hex
*8
B1 hex
*9
--- 4 bytes
0000 0000 to
FFFF FFFF hex
(0 to
4294967295
decimal)
Write Writes the set value
for the total ON time
(unit: s) or number
of contact opera-
tions (unit: opera-
tions) for the output
(0 to 3, or 0 to 7 for
an Eight-output
Unit) specified by
the Attribute ID.
10 hex 8E hex 01 to 40
hex
*1
78 hex
*2
7B hex
*3
7E hex
*4
81 hex
*5
A8 hex
*6
AB hex
*7
AE hex
*8
B1 hex
*9
4 bytes
0000 0000 to
FFFF FFFF hex
(0 to
4294967295
decimal)
---
Read Out-
put Mainte-
nance
Counter
Read Reads the total ON
time (unit: s) or
number of contact
operations (unit:
operations) for the
output (0 to 3, or 0
to 7 for an Eight-out-
put Unit) specified
by the Attribute ID.
0E hex 8E hex 01 to 40
hex
*1
77 hex
*2
7A hex
*3
7D hex
*4
80 hex
*5
A7 hex
*6
AA hex
*7
AD hex
*8
B0 hex
*9
--- 4 bytes
0000 0000 to
FFFF FFFF hex
(0 to
4294967295
decimal)

Table of Contents

Related product manuals