312
Explicit Messages Appendix A
Number of
AD Conver-
sion Points
Setting
Write/
Read
Sets the number of AD
conversion points.
Write:
10 hex
Read:
0E hex
8F hex 01 to 40
hex
*1
64 hex 2 bytes 1 byte
Input
Range Set-
ting
Write/
Read
Sets the input range.
10 to 10 V: 0
0 to 5 V: 1
0 to 10 V: 2
4 to 20 mA: 3
1 to 5 V: 7
0 to 20 mA: 8
Write:
10 hex
Read:
0E hex
8F hex 01 to 04
hex
*1
66 hex
*2
8E hex
*3
1 byte 1 byte
Analog Sta-
tus Flag
Read
Read Reads the status of the
Analog Status Flags.
LL = 0; L = 1;
Pass signal = 2; H = 3;
HH = 4; Valley shot = 5;
Top shot = 6;
Off-wire detection = 7
0E hex 8F hex 01 to 40
hex
*1
69 hex
*2
91 hex
*3
1 byte
Analog
Data 1 Allo-
cation
Selection
Write/
Read
Selects the data allo-
cated to Analog Data 1.
Analog input value: 0;
Peak value: 1;
Bottom value: 2;
Top value: 3;
Valley value: 4;
Rate of change value: 5
Write:
10 hex
Read:
0E hex
8F hex 01 to 40
hex
*1
6B hex
*2
93 hex
*3
1 byte 1 byte
Analog
Data 2 Allo-
cation
Selection
Write/
Read
Selects the data allo-
cated to Analog Data 2.
Analog input value: 0;
Peak value: 1;
Bottom value: 2;
Top value: 3;
Valley value: 4;
Rate of change value: 5
Write:
10 hex
Read:
0E hex
8F hex 01 to 40
hex
*1
6C hex
*2
94 hex
*3
1 byte 1 byte
Function
Setting
Write/
Read
Sets each function.
Bit status:
ON: Enabled,
OFF: Disabled
Moving average: 0;
Scaling: 1;
Peak/bottom hold: 2;
Top/valley hold: 3;
Comparator: 4;
Cumulative counter: 5;
Rate of change: 6
Write:
10 hex
Read:
0E hex
8F hex 01 to 40
hex
*1
6D hex
*2
95 hex
1 byte 1 byte
Scaling
Type Set-
ting
Write/
Read
Default scaling: 0:
User scaling: 1
Write:
10 hex
Read:
0E hex
8F hex 01 to 40
hex
*1
6E hex
*2
96 hex
1 byte 1 byte
Scaling
Point 1 Set-
ting
Write/
Read
Sets an analog value as
the 0% value for user
scaling.
Write:
10 hex
Read:
0E hex
8F hex 01 to 40
hex
*1
6F hex
*2
97 hex
*3
2bytes
(28000 to
28000)
2bytes
(28000 to
28000)
Scaling
Point 2 Set-
ting
Write/
Read
Sets an analog value as
the 100% value for user
scaling.
Write:
10 hex
Read:
0E hex
8F hex 01 to 40
hex
*1
70 hex
*2
98 hex
*3
2bytes
(28000 to
28000)
2bytes
(28000 to
28000)
Explicit
message
Read
/write
Function Command Response
Service
code
Class
ID
Instance
ID
Attribute ID Data