311
Explicit Messages Appendix A
Setting Hold/Clear for Communications Errors (Output)
Note (1) The default setting is for all outputs to be cleared (0).
(2) Bit numbers correspond to output numbers, e.g., bit 00 corresponds to output 0.
Writing Maintenance Information
Explicit Messages for Analog Slaves
Setting and Reading for Analog Input Units
Explicit
message
Read/
write
Function Command Response
Service
code
Class
ID
Instance
ID
Attribute
ID
Data size
Setting for
Output Sta-
tus (Hold or
Clear) after
Slice Bus
Error
*1
Read Reads whether
each output’s sta-
tus will be cleared or
held when there is a
slice bus error.
0E hex 8E hex 01 to 40
hex
83 hex --- 4 bytes
Status of bits 00 to
32.
*2
0: Clear
1: Hold
Write Sets whether each
output’s status will
be cleared or held
when there is a slice
bus error.
10 hex 8E hex 01 to 40
hex
83 hex 4 bytes
Settings for
bits 00 to 32
*2
0: Clear
1: Hold
---
Setting for
Output Sta-
tus (Hold or
Clear) after
Host Net-
work Com-
munications
Error
*1
Read Reads whether
each output’s sta-
tus will be cleared or
held when there is a
host network com-
munications error.
0E hex 8E hex 01 to 40
hex
84 hex --- 4 bytes
Status of bits 00 to
32.
*2
0: Clear
1: Hold
Write Sets whether each
output’s status will
be cleared or held
when there is a host
network communi-
cations error.
10 hex 8E hex 01 to 40
hex
84 hex 4 bytes
Settings for
bits 00 to
32.
*2
0: Clear
1: Hold
---
Explicit
message
Read/
write
Function Command Response
Service
code
Class
ID
Instance
ID
Attribute
ID
Data size
Mainte-
nance
Counter
Save
Save Records the mainte-
nance counter in the
Slice I/O Unit's
memory.
16 hex 8D hex 01 to 40
hex
*1
71 hex -- ---
Explicit
message
Read
/write
Function Command Response
Service
code
Class
ID
Instance
ID
Attribute ID Data
Analog
Data 1
Value
Read Reads the value for
Analog Data 1.
0E hex 8F hex 01 to 40
hex
*1
65 hex
*2
8D hex
*3
2 byte
Analog
Data 2
Value
Read Reads the value for
Analog Data 2.
0E hex 8F hex 01 to 40
hex
*1
68 hex
*2
90 hex
*3