310
Explicit Messages Appendix A
Setting and Monitoring the Operation Time
Note (1) The Instance ID specifies the Slice I/O Unit’s unit number (1 to 63 decimal).
(2) Specifies operation time 1.
(3) Specifies operation time 2.
(4) Reads data for both operation time 1 and operation time 2 (operation times 1, 2, 3, and 4 for Units
with 8 inputs).
(5) Specifies input 3 (only for Units with 8 inputs).
(6) Specifies input 4 (only for Units with 8 inputs).
Explicit
message
Read/
write
Function Command Response
Service
code
Class
ID
Instance
ID
Attribute
ID
Data size
Set Value
for Opera-
tion Time
Monitor
Read Reads the monitor
set value for the
operation time (unit:
ms) specified by the
Attribute ID.
0E hex 8E hex 01 to 40
hex
*1
8B hex
*2
93 hex
*3
B4 hex
*5
BC hex
*6
--- 2 bytes
0000 to FFFF
hex
(0 to 65,535
decimal)
Write Writes the monitor
set value for the
operation time (unit:
ms) specified by the
Attribute ID.
10 hex 8E hex 01 to 40
hex
*1
8B hex
*2
93 hex
*3
B4 hex
*5
BC hex
*6
2 bytes
0000 to FFFF
hex
(0 to 65,535
decimal)
---
Present
Value for
Operation
Time Moni-
tor
Read Reads the present
value for the opera-
tion time (unit: ms)
specified by the
Attribute ID.
0E hex 8E hex 01 to 40
hex
*1
8A hex
*2
92 hex
*3
B3 hex
*5
BB hex
*6
--- 2 bytes
0000 to FFFF
hex
(0 to 65,535
decimal)
Monitor
Status for
Operation
Time Moni-
tor
Read Reads the monitor
status for the opera-
tion time (unit: ms)
specified by the
Attribute ID.
0E hex 8E hex 01 to 40
hex
*1
87 hex
*4
--- 2 bytes
0000 to FFFF
hex
(0 to 65,535
decimal)
Operation
Time Moni-
tor Peak
Value Read
Read Reads the peak
value for the opera-
tion time (unit: ms)
specified by the
Attribute ID.
0E hex 8E hex 01 to 40
hex
*1
8C hex
*2
94 hex
*3
B5 hex
*5
BD hex
*6
--- 2 bytes
0000 to FFFF
hex
(0 to 65,535
decimal)
Operation
Time Moni-
tor Peak
Value
Reset
Reset Resets to the
present value the
peak value for the
operation time (unit:
ms) specified by the
Attribute ID.
05 hex 8E hex 01 to 40
hex
*1
8C hex
*2
94 hex
*3
B5 hex
*5
BD hex
*6
2 bytes
0000 to FFFF
hex
(0 to 65,535
decimal)
---
Operation
Time Moni-
tor History
Read
Read Reads the history of
the monitor status
for the operation
time (unit: ms) spec-
ified by the Attribute
ID.
0E hex 8E hex 01 to 40
hex
*1
8F hex
*2
97 hex
*3
B8 hex
*5
C0 hex
*6
--- 1 byte
00 hex: Value
not exceeded
01 hex: Value
exceeded
Operation
Time Moni-
tor History
Reset
Reset Resets to 0 the his-
tory of the monitor
status for the opera-
tion time (unit: ms)
specified by the
Attribute ID.
05 hex 8E hex 01 to 40
hex
*1
8F hex
*2
97 hex
*3
B8 hex
*5
C0 hex
*6
--- ---