324
Explicit Messages Appendix A
Digital Out-
put Mainte-
nance
Counter Set
Values
Read Reads the set val-
ues for the total
ON time (unit: s)
or number of con-
tact operations
(unit: operations)
for digital out-
puts.
*2
0E hex 8E hex 01 to 40
hex
*1
OUT0:
79 hex
OUT1:
7D hex
--- 4 bytes
0000 0000 to
FFFF FFFF hex
(0 to
4,294,967,295
decimal)
Write Writes the set val-
ues for the total
ON time (unit: s)
or number of con-
tact operations
(unit: operations)
for digital out-
puts.
*2
10 hex 8E hex 01 to 40
hex
*1
OUT0:
79 hex
OUT1:
7D hex
4 bytes
0000 0000 to
FFFF FFFF hex
(0 to
4,294,967,295
decimal)
---
Output
Power Sup-
ply Monitor
Read Reads the status
of the input power
supply.
If there is more
than one output
power supply, an
AND of the sta-
tus of all the out-
put power
supplies is
returned.
0E hex 8E hex 01 to 40
hex
*1
82 hex --- 1 byte
00 hex: OFF
01 hex: ON
Terminal
Mainte-
nance Infor-
mation
Monitor
Mode of
Digital Out-
puts
Read Reads the moni-
tor mode for
maintenance
information on
digital outputs.
*2
0E hex 8E hex 01 to 40
hex
*1
83 hex --- 4 bytes
Status of bits 00
(output 0) and 01
(output 1) of 1st
byte:
0: Total ON time
mode
1: Contact opera-
tion counter mode
Write Writes the moni-
tor mode for
maintenance
information for
digital outputs.
*2
10 hex 8E hex 01 to 40
hex
*1
83 hex 4 bytes
Status of bits 00
(output 0) and 01
(output 1) of 1st
byte:
0: Total ON time
mode
1: Contact opera-
tion counter mode
---
Monitor Sta-
tus of Digital
Output
Mainte-
nance
Counter
Read Reads the moni-
tor status for total
ON time or num-
ber of contact
operations of digi-
tal outputs.
*2
0E hex 8E hex 01 to 40
hex
*1
84 hex --- 4 bytes
Status of bits 00
(output 0) and 01
(output 1) of 1st
byte:
0: In range
1: Out-of-range
(over the monitor
value)
Counter
Value
Read Reads the
present counter
value.
0E hex 8E hex 01 to 40
hex
*1
87 hex --- 4 bytes
Range of values:
2,147,483,648 to
2,147,483,647
Explicit
message
Read/
write
Function Command Response