Loading...
323
Explicit Messages Appendix A
Terminal
Mainte-
nance Infor-
mation
Mode Moni-
tor of Digital
Input
Read Reads the moni-
tor mode for
maintenance
information on the
digital input.
0E hex 8E hex 01 to 40
hex
*1
71 hex --- 4 bytes
Status of bit 00 of
1st byte:
0: Total ON time
mode
1: Contact opera-
tion counter mode
All other bits will
be 0.
Write Writes the moni-
tor mode for
maintenance
information for
the digital input.
10 hex 8E hex 01 to 40
hex
*1
71 hex 4 bytes
Status of bit 00 of
1st byte:
0: Total ON time
mode
1: Contact opera-
tion counter mode
Set all other bits
to 0.
---
Monitor Sta-
tus of Digital
Input Main-
tenance
Counter
Read Reads the moni-
tor status for the
total ON time or
number of contact
operations for the
digital input.
0E hex 8E hex 01 to 40
hex
*1
72 hex --- 4 bytes
Status of bit 00 of
1st byte:
0: In range
1: Out-of-range
(over the monitor
value)
Monitor Dig-
ital Output
Status
Read Reads the current
status of digital
outputs.
*2
0E hex 8E hex 01 to 40
hex
*1
OUT0:
76 hex
--- 1 byte
00 hex: OFF
01 hex: ON
Digital Out-
put Names
Read Reads the com-
ments set for digi-
tal outputs.
*2
0E hex 8E hex 01 to 40
hex
*1
OUT0:
77 hex
--- 1 to 32 bytes
Contains stored
comment in
ASCII.
Write Writes the com-
ments for digital
outputs.
*2
10 hex 8E hex 01 to 40
hex
*1
OUT0:
77 hex
1 to 32 bytes
The comment to
set in ASCII.
---
Digital Out-
put Mainte-
nance
Counter
Read Reads the total
ON time (unit: s)
or number of con-
tact operations
(unit: operations)
for digital out-
puts.
*2
0E hex 8E hex 01 to 40
hex
*1
OUT0:
78 hex
OUT1:
7C hex
--- 4 bytes
0000 0000 to
FFFF FFFF hex
(0 to
4,294,967,295
decimal)
Write Writes the total
ON time (unit: s)
or number of con-
tact operations
(unit: operations)
for digital out-
puts.
*2
0 hex 8E hex 01 to 40
hex
*1
OUT0:
78 hex
OUT1:
7C hex
4 bytes
0000 0000 to
FFFF FFFF hex
(0 to
4,294,967,295
decimal)
---
Reset Resets the total
ON time (unit: s)
or number of con-
tact operations
(unit: operations)
for digital out-
puts.
*2
05 hex 8E hex 01 to 40
hex
*1
OUT0:
78 hex
OUT1:
7C hex
--- ---
Explicit
message
Read/
write
Function Command Response
Service
code
Class
ID
Instance
ID
Attribute
ID
Data size

Table of Contents