D-100 Network Interface Module with BACnet MS/TP Interface
Protocol Implementation Conformance Statement (PICS)
BACnet Protocol
Date: July 1, 2009
Vendor Name: ONICON Incorporated
Product Name: D-100-BAC Network Interface Module
Product Model: D-100-BAC
Product Description:
The D-100 Flow Display with Network Interface is a flexible platform designed to provide semi-custom solutions to difficult
network interface problems. The standard module includes an internal power supply in a NEMA 13 wall mounted enclosure. A variety of optional interface
modules allows for simultaneous connection to multiple networks from one device or provides network access for non-networked sensors.
BACnet Standardized Device Profile (Annex L):
⌧ BACnet Smart Sensor (B-SS)
⌧ BACnet Smart Actuator (B-SA)
⌧ BACnet Application Specific Controller (B-ASC)
BACnet Interoperability Building Blocks Supported (Annex K):
⌧ K.1.2 BIBB – Data Sharing – ReadProperty-B (DS-RP-B)
⌧ K.1.8 BIBB – Data Sharing – WriteProperty-B (DS-WP-B)
⌧ K.5.2 BIBB – Device Management – Dynamic Device
Binding-B (DM-DDB-B)
Segmentation Capability:
None
Standard Object Types Supported:
⌧ Device Object ⌧ Multi State Input Output
⌧ Analog Input ⌧ Multi State Output
⌧ Analog Output ⌧ Multi State Value
⌧ Analog Value
⌧ Binary Input
⌧ Binary Output
⌧ Binary Value
For all these properties the following apply:
1. Does not support BACnet CreatObject
2. Does not support BACnet DeleteObject
3. Does not support any optional properties
4. No additional writeable properties exist
5. No proprietary properties exist
6. No range restrictions exist
Data Link Layer Options:
⌧ MS/TP master (Clause 9), baud rate up to 76800 bps
⌧ MS/TP slave (Clause 9), baud rate up to 76800 bps
Device Address Binding:
Not supported
Character Sets Supported:
⌧ ANSI X3.4.