D-100 Flow Display Manual 08/12 - 0634-7 Page 6
GENERAL SPECIFICATIONS
ACCURACY
Analog Inputs: 0.1% of full scale
Analog Outputs: 0.1% of full scale
PROGRAMMING
Factory programmed for specic application.
MEMORY
Nonvolatile EEPROM memory retains all program
parameters and totalized values in the event of
power loss.
DISPLAY
Standard: 2-line Alphanumeric LCD displays ow
rate and ow total for the standard ow input
Alpha: 16 character, 0.2” high
Numeric: 7 digit, 0.4” high
Rate Display Range: 0 - 9,999,999
Totalizer Display Range: 0 - ,999,999
The totalizers will roll over to zero when maximum
count is exceeded.
OUTPUT SIGNALS
Pulse Outputs:
Two isolated contact closure outputs for separately
totalizing forward and reverse ow from the
standard ow input. Contact duration: 0.5, 1, 2
or 6 seconds (factory selectable). Default: 0.5
seconds
Maximumcontactratings:100mA,50VDC
Isolated contact closure output for indicating ow
direction
Maximumcontactratings:100mA,50VDC
Analog Outputs Options:
Single isolated analog output:
4-20mA,0-10Vor0-5V
Multiple (4) isolated analog outputs: 4-20 mA,
0-10Vor0-5Voutputs
Network Interface Options
MODBUS RTU RS485
MODBUS RTU TCP/IP
BACnet MS/TP
BACnet UDP/IP
LONWORKS FTT10A
JCI Metasys - N2
Siemens Apogee - P1 FLN
INPUT SIGNALS
Standard: One totalizing ow input:
4-20 mA, contact closure or pulse
One contact closure input for ow
direction
Optional: Two auxiliary analog rate inputs:
4-20 mA
One auxiliary totalizer input: pulse or
contact closure
TEMPERATURE RANGE
Ambient temperature range: -20° F to 140° F
Do not install in direct sunlight.
MAINTENANCE
ONICON recommends periodic inspection and
recalibration for sensors connected to the D-100.
No other periodic maintenance is required for the
main unit.
MECHANICAL
Electronics Enclosure:
Standard: Steel NEMA 13, wall mount, 8”x10”x4”
Optional: NEMA 4
ELECTRICAL
This equipment is intended for INSTALLATION
CATEGORY(OVERVOLTAGECATEGORY)II
applications.
INPUT POWER - FACTORY SELECTABLE:
230VAC50Hz,125mA
120VAC50/60Hz,250mA
24±4VAC50/60Hz,650mA
21.6-28VAC50/60Hz,650mAwhenusingthe
F-3500 with an optional multi-analog
output board
INTERNAL FUSE RATINGS:
230VAC-3AG,1/8Amp,250Volt,Fastacting
120VAC-3AG,1/4Amp,250Volt,Fastacting
24VAC-3AG,3/4Amp,250Volt,Fastacting
INTERNAL SUPPLY:
Provides24VDC,250mAmaximumtoelectronics
and sensors
OVERCURRENTPROTECTIVEDEVICERATINGS:
Supply mains overcurrent protective devices with
the following ratings:
120VAC50/60Hz–15A
230VAC50Hz–6A
SENSOR WIRING:
Flow Signal: Use 18-22 gage twisted shielded pair
suitable for the length of run and required
maximum current carrying capacity.
24±4VacInputPower:UsePVCjacketedcopper
cable with a wire gage suitable for the length of
run and required maximum current carrying
capacity. The installation must comply with all
local, state and federal building codes.
120/230VACInputPower:Useathreewire
service with one wire as a protective earth
ground. The installation must comply with all
local, state and federal building codes.
Note:Specicationsaresubjecttochangewithoutnotice