INTELLIGENT PDU USER MANUAL
Figure 26: Energy Threshold
3. Select and enter the appropriate thresholds in kilowatts and click Save.
• Upper Critical (kWh)
• Upper Warning (kWh)
• Reset Threshold (kWh)
• Alarm State Change Delay (samples)
If enabled, the PDU asserts any warning or critical condition only after a
specified number of consecutive samples that cross a threshold are
generated. This prevents several threshold alerts from being generated if the
measurements return to normal immediately after rising above an upper
threshold or dropping below a lower threshold.
4. Repeat steps 1 - 3 for all PDUs.