INTELLIGENT PDU USER MANUAL
37
For example, the current critical threshold for the input phase is set to 19
voltage (V). The current draw rises to 20V, triggering a Current Critical alert.
The current then continues to fluctuate between 18.1V and 20V. With the
reset threshold set to 1V, the PDU continues to indicate that the current on
the input phase is above critical. Without a reset threshold (that is, the reset
threshold is set to zero), the PDU would de-assert the condition each time the
current dropped to 18.9V, and re-assert the condition each time the current
reached 19A or higher. With the fluctuating current, this could result in
repeating event notifications, such as SNMP traps, SMTP alerts or Syslog
notifications.
Alarm State Change Delay (samples)
If enabled, the PDU asserts any warning or critical condition only after a
specified number of consecutive samples that cross a threshold are
generated. This prevents several threshold alerts from being generated if the
measurements return to normal immediately after rising above an upper
threshold or dropping below a lower threshold.
4. Repeat steps 1 - 3 for all phases.
Circuit Breaker Alarm Threshold
The PANDUIT PDU will send alert notifications when a circuit breaker amperage
crosses above or below the settings you specify in the Circuit Breaker Alarms
configuration:
1. Go to the Thresholds > Circuit Breaker Page.
2. Click the pencil for the Circuit Break to update.

Table of Contents

Other manuals for Panduit smartzone G5

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Panduit smartzone G5 and is the answer not in the manual?

Panduit smartzone G5 Specifications

General IconGeneral
BrandPanduit
Modelsmartzone G5
CategoryPower distribution unit
LanguageEnglish