14.4 North American & Canadian Compliance Information (Frame 1-5 only)
14.4.1 UL Standards
The UL/cUL mark applies to products in the United States and Canada and it means that UL has
performed product testing and evaluation and determined that their stringent standards for product
safety have been met. For a product to receive UL certication, all components inside that product
must also receive UL certication:
14.4.2 UL Standards Compliance
This drive is tested in accordance with UL standard UL508C, File No. E142140 and complies with
UL requirements. To ensure continued compliance when using this drive in combination with other
equipment, meet the following conditions:
1. Do not install the drive to an area greater than pollution severity 2 (UL standard).
2. Installation and operating instructions shall be provided with each device.
The following markings shall appear in one of the following locations; shipped separately with the
device; on a separable, self-adhesive permanent label that is shipped with the device; or anywhere on
the device itself:
a) Designation markings for each wiring diagram
b) Markings for proper wiring connections
c) “Maximum surrounding air temperature 40
º
C” or equivalent
d) “Solid state motor overload protection reacts when reaches 150% of FLA” or equivalent
e) “Install device in pollution degree 2 environment.” Or equivalent
f) “Suitable for use on a circuit capable of delivering not more than 5,000 rms symmetrical amperes,
480/240 volts maximum when protected by made by COOPER BUSSMANN LLC Class T Fuse.” Or
equivalent. Recommended input fuse selection listed below:
g) “Integral solid state short circuit protection does not provide branch circuit protection. Branch circuit
protection must be provided in accordance with the National Electrical Code and any additional local
codes” or equivalent
h) “CAUTION – Risk of Electric Shock” should be provided, followed by instructions to discharge the
Bus Capacitor or indicating the time required (5 minutes) for Bus Capacitor to discharge to a level
below 50Vdc
i) “Drives have no provision for motor over temperature protection” or equivalent
j) For use in Canada only: “TRANSIENT SURGE SUPPRESSION SHALL BE INSTALLED ON THE
LINE SIDE OF THIS EQUIPMENT AND SHALL BE RATED ____480/240 ___V (PHASE TO GROUND),
480/240V (PHASE TO PHASE), SUITABLE FOR OVERVOLTAGE CATEGORY _III___, AND SHALL
PROVIDE PROTECTION FOR A RATED IMPULSE WITHSTAND VOLTAGE PEAK OF _ 6Kv” or
equivalent
k) Field wiring terminal markings – Wiring terminals shall be marked to indicate the proper connections
for power supply and load, or a wiring diagram coded to the terminal marking shall be securely
attached to the device
l) “Use 60/75ºC CU wire” or equivalent
m) Required wire torque, type and range listed in drive installation manual.
Compliance 6-1

Other manuals for Parker AC10 series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Parker AC10 series and is the answer not in the manual?

Parker AC10 series Specifications

General IconGeneral
Overload Capacity150% for 60 seconds
Analog Inputs2
Analog Outputs1
Communication OptionsModbus RTU
Protection RatingIP20
Input Voltage200-240VAC, 380-480VAC, 500-575VAC, 600VAC, 690VAC
Digital Outputs2
ProtectionOvercurrent, Overvoltage, Undervoltage, Overtemperature, Short Circuit
Operating Temperature-10°C to +50°C
Humidity5% to 95% (non-condensing)
DimensionsVaries by model
WeightVaries by model
BrakingBuilt-in dynamic braking