10-1 Parameter List and Default Settings
Function
Code
Function Denition Setting Range Mfr’s Value Change
F100 User’s Password 0-9999
F102 Inverter’s Rated Current (A)
Subject
to inverter
model
*
F103 Inverter Power (kW)
Subject
to inverter
model
*
F104 Reserved
F105 Software Edition No.
Subject
to inverter
model
D
F106 Control Mode
Setting range:
0:Sensorless
vector control
(SVC);
1: Reserved;
2: VVVF
3: Vector control
1
6: PMSM
sensorless
vector control
2
X
F107 Password Protection
0: Disabled; 1:
Enabled
0
F108 User’s Password 0-9999 8
F109 Starting Frequency (Hz) 0.0-10.00Hz 0.0
F110
Holding Time of Starting
Frequency (S)
0.0-999.9 0.0
F111 Max Frequency (Hz) F113-590.0Hz 50.00
F112 Min Frequency (Hz) 0.00Hz-F113 0.50
F113 Target Frequency (Hz) F112-F111 50.00
F114 1
st
Acceleration Time (S) 0.1-3000
Subject
to inverter
model
F115 1
st
Deceleration Time (S) 0.1-3000
F116 2
nd
Acceleration Time (S) 0.1-3000
F117 2
nd
Deceleration Time (S) 0.1-3000
F118 Base Frequency (Hz) 15.00-590.0 50.00
X
F119
Setting Accel/Decel
Reference Time
0: 0~50.00Hz
1: 0~ F111
0
X
F120
Forward/Reverse
Switchover Dead-Time
0.0-3000 0.0