Function
Code
Function Denition Setting Range Mfr’s Value Change
F210 Frequency display accuracy 0.01-2.00 0.01
F211 Speed of digital control 0.01-100.00Hz/s 5.00
F212 Direction memory
0: Disabled 1:
Enabled
0
F213
Auto-start after repowered
up
0: Disabled 1:
Enabled
0
F214 Auto-start after reset
0: Disabled 1:
Enabled
0
F215 Auto-start delay time 0.1-3000.0 60.0
F216 Auto-start restart attempts 0-5 0
F217 Fault reset delay 0.0-10.0 3.0
F218 Reserved
F219 Write EEPROM by Modbus
1: Disabled; 0:
Enabled
1
F220
Frequency memory after
power-down
0: Disabled 1:
Enabled
0
F221-
F223
Reserved
F224
When target frequency is
lower than min frequency
0: Stop
1: run at min freq
1
F225-
F227
Reserved
F228 Application selection
0: Invalid
1: Basic speed
control
2: auto/manual
control
3: Stage speed
control
4: Terminal
control;
5: PID control;
No Macro
selected
F229-
F230
Reserved
Parameter List and Default Settings
10-6

Other manuals for Parker AC10 series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Parker AC10 series and is the answer not in the manual?

Parker AC10 series Specifications

General IconGeneral
Overload Capacity150% for 60 seconds
Analog Inputs2
Analog Outputs1
Communication OptionsModbus RTU
Protection RatingIP20
Input Voltage200-240VAC, 380-480VAC, 500-575VAC, 600VAC, 690VAC
Digital Outputs2
ProtectionOvercurrent, Overvoltage, Undervoltage, Overtemperature, Short Circuit
Operating Temperature-10°C to +50°C
Humidity5% to 95% (non-condensing)
DimensionsVaries by model
WeightVaries by model
BrakingBuilt-in dynamic braking