3. Specifications
LOOP Resistance
L- PE (Hi-Amp)
±(4% of reading+ 6digits)
Measuring Current …………….………………………………………..………… 8.0 A ~ 25 A
Range of the Voltage Used …………………………….……195V AC – 260V AC (50,60Hz)
L- PE (No Trip)
±(5% of reading+ 6 digits)
Measuring Current ……………..………………………………………………… < 15mA
Range of the Voltage Used ……………………………195V AC– 260V AC (50,60Hz)
LINE Resistance
L- N
±(4% of reading+ 6digits)
Measuring Current …………….………………………………………………… 4.0 A
Range of the Voltage Used ………………………..195V AC – 260V AC (50,60Hz)
RCD (EN 61557-6)
Rcd Rating (I
n
) …………...………………………..10mA, 30mA, 100mA, 300mA, 500mA and 1A.
Test current …………………………………..……x1/2, x1, x2 and x5
-52-