EasyManuals Logo

pleiger 362MC User Manual

pleiger 362MC
58 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #17 background imageLoading...
Page #17 background image
Pleiger Elektronik
GmbH & Co. KG
Edition: 6/2007 Subject to modifications Manual for 362MC Page: 17
Controller 362MC Typ: 2PntPW Actuator Controlled system
Wxd Y X
PID
Controller 362MC Typ: 2Point Actuator Controlled system
Wxd Y X
PID
PID
Controller 362MC Typ: 3PntPW Actuator Controlled system
Wxd Y X
PID
Controller 362MC Typ: 3Point Actuator Controlled system
Wxd Y X
5.5.1 Explanatory note on controller types
The controller type “CtrlTyp” can be defined separately for each of the 362MC´s two controllers.
2-Point controller = switching controller with 2 switching output states, relay+ ON and relay+ OFF.
The 2-Point controller with feedback “2PntPW” operates internally as a continuous controller with
down-line pulse-width modulator and switching output. Its output corresponds to the ratio of ON period
to OFF period of relay+ of assigned relay set 1 or 2.
In the case of the 2-Point controller without feedback “2Point” the pulse-width modulator is replaced by
a threshold switch with hysteresis.
3-Point controller = switching controller with 3 switching output states, relay+ ON, relay+ and relay OFF
and relay- ON. The 3-Point controller with feedback “3PntPW” operates internally as a continuous
controller with two down-line pulse-width modulators and two switching outputs. Its output corresponds
to the ratio of ON period to OFF period of relay+ if the controller output is positive and relay- if negative,
both relay+ and relay- being from assigned relay set 1 or 2.
In the case of the 3-Point controller without feedback “3Point” the pulse-width modulator is replaced by
a threshold switch with hysteresis.
The two switching outputs can be parameterised separately, whereby the controller and output+ use the
complete 1
st
parameter set (
1
) and output- uses only the separate loop gain, Kr, and the parameters for
the switching outputs of the 2
nd
parameter set (
2
). See table: