10 Technical data
Voltage supply Standard Optional
Input voltage 230V AC ±10% 115V AC ±10%
Frequency 50 - 60Hz ±5%
Stromaufnahme max. 100mA (* max. 200mA (* +switching current)
Permissible ambient temperature
Operating temperature 0 - +60°C
Storage temperature -20 - +85°C
Protection type
Housing and terminals IP00
Frontside IP30
Housing
Type Housing for installation in Wall-mounting housing
Dimensions 144x72 mm acc.DIN 43700 Dimension sheet available
installation depth 140 mm on request
Control panel cut-out 137
+0.5
mm x 65.5
+0.5
mm
Weight approx. 1200 g
Analogue inputs (only 1
st
input) (only 1
st
input)
1
st
and 2
nd
input (PT100 inputs) Pt100 4 - 20mA
Measuring range 0 - 200°C 0 - 500°C 0-100%
Resolution 0.2°C 0.5°C 20µA
Measuring accuracy ±0.5%
3
rd
input (current/voltage input)
Measuring range 0(4) - 20mA 0 - 5V, 0 - 10V
Resolution 20µA 5 / 10mV
Measuring accuracy ±0.5%
Internal resistance 250 Ohm
4
th
input (resistance input)
Measuring range 0 - 200 Ohm
Resolution 0.2 Ohm
Measuring accuracy ±0.5%
Binary inputs
Type 6 x optocoupler inputs
for floating contacts for 24V DC nominal inputs
(electrically isolated switching (switching voltage external)
voltage supplied)
Operating threshold 12V ±4V
Switching current 1mA ±0.5mA
Switching outputs
Type 1 x relay set (expandable by 2
nd
relay set)
each with relay +(OPEN) and -(CLOSED)
Switching voltage = supply voltage floating contacts
(internal connected) (external supply and fusing)
Max. contact current 1A at 230V-AC max. 8A and max. 250V
2A at 115V-AC purely resistive load only
Type 1 x alarm relay with floating changeover contact
Analogue outputs (hardware extension)
Type 2 x current output 2 x voltage output
Output range 0(4) - 20mA, ±20mA 0 - 10V, ±10V
Resolution 40µA 20mV
Accuracy ±0.5%
Load impedance max. 400 Ohm min. 1 kOhm
Communication interface (hardware extension)
Type RS485 isolated RS422 isolated

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the pleiger 362MC and is the answer not in the manual?

pleiger 362MC Specifications

General IconGeneral
Brandpleiger
Model362MC
CategoryController
LanguageEnglish