POWER ELECTRONICS SD450 - DEVICENET
CONFIGURATION OF DEVICENET OPTIONAL BOARD
19
ENGLISH
4.2. Parameter Setting of DeviceNet
4.2.1. DeviceNet ID Setting (COM-10 Î MAC ID)
It allows assigning the equipment number (station address) to each
inverter into a DeviceNet network. Therefore, this number is unique
and for this reason is necessary to be sure that each equipment has
a different address.
The setting of this parameter is available from the keypad. The
default value is ‘63’. If DPRAM communication between inverter and
the optional board becomes faulty, the value will default to ‘63’.
When the value of this parameter is changed during run, the optional
board is automatically reset to find the new address device in the
network. If a duplicated address is found, the NS led (Network
Status) turns solid red. In this case, the address value must be
changed. In the normal operation, NS led is flashing green.