SD450 - DEVICENET POWER ELECTRONICS
62
ADDRESS LIST
Address Range
16 bit 10 bit
Screen Description
Default
value
Option Values
972E 38702
APP-46
Sleep
Freq5
Sleep frequency 5 0
0 – FU1-
30
972F 38703
APP-47
Sleep
Freq6
Sleep frequency 6 0
0 – FU1-
30
9730 38704
APP-48
Sleep
Freq7
Sleep frequency 7 0
0 – FU1-
30
9731 38705
APP-49
WakeUp level
Wake up level for Sleep mode 20 0 – 1000
9732 38706
APP-50
Start Freq 1
Start frequency of auxiliary
motor 1
4950
0 – FU1-
30
9733 38707
APP-51
Start Freq 2
Start frequency of auxiliary
motor 2
4950
0 – FU1-
30
9734 38708
APP-52
Start Freq 3
Start frequency of auxiliary
motor 3
4950
0 – FU1-
30
9735 38709
APP-53
Start Freq 4
Start frequency of auxiliary
motor 4
4950
0 – FU1-
30
9736 38710
APP-54
Stop Freq 1
Stop frequency of auxiliary
motor 1
2000
0 – FU1-
30
9737 38711
APP-55
Stop Freq 2
Stop frequency of auxiliary
motor 2
2000
0 – FU1-
30
9738 38712
APP-56
Stop Freq 3
Stop frequency of auxiliary
motor 3
2000
0 – FU1-
30
9739 38713
APP-57
Stop Freq 4
Stop frequency of auxiliary
motor 4
2000
0 – FU1-
30
973A 38714
APP-58
Aux start DT
Delay time before connecting
auxiliary motors
50 0 – 9999
973B 38715
APP-59
Aux stop DT
Delay time before stopping
auxiliary motors
50 0 – 9999
973C 38716
APP-60
AUX AccTime
Time for the ramp at
connecting auxiliary motors
20 0 – 6000
973D 38717
APP-61
AUX DecTime
Time for the ramp at
disconnecting auxiliary motors
20 0 – 6000
9742 38722
APP-66
AutoCh_Mode
Rotation mode of auxiliary
motors
0 0 – 2
9743 38723
APP-67
AutoEx-intv
Operation time of the inverter
for one of the motors
4320 0 - 5940
No
9745 38725
APP-69
Inter-lock
Detection of motors out of
service
0
Yes
0 – 1
9747 38727
APP-71
Aux STT FB
Difference for starting auxiliary
motors
2 0 – 100
9748 38728
APP-72
Aux STP FB
Difference for stopping auxiliary
motors
0 0 – 100