Part Number 6300-095D Page 29 of 43
Single mSensor and Block with 2 Terminals
Single
mSensor
Power Lead
Wires
Wire
Function / Block Connection
Red Positive Power wire for sensor.
Connect to positive terminal of Block.
Brown Positive Sense wire for Block.
Blue Negative Sense wire for Block.
Black Power return wire for sensor.
Connect to negative terminal of Block.
Please note the following important points:
The power lead is manufactured with cable ties in order to keep the Sense wire pairs and the Power wires
closely coupled.
Try to keep the Sense wire pairs and Power wires closely coupled as much as possible.
Where possible, do not remove the cable ties.
The cable ties nearest the block terminals may be need to be repositioned to allow the wires to be
connected to the block terminals.